DISC INSULATORS FOR TRANSMISSION LINES

DISC INSULATORS FOR TRANSMISSION LINES
Voltage
Normal suspension
Normal Tension
No.of discs
UTS
No.of discs
UTS
66 kV
5
45 kN
6
50 kN
110 kV
7
70 kN
8
90 kN
220 kV
14
90 kN
15
120 kN
400 kV
23
115 kN
2x23
165 kN